When you need a motor to stop fast on our SHZK 300N series drives, you basically have two options on the production floor: vfd dc injection braking built into the drive’s firmware, or dynamic braking through an external resistor wired to the P+/PB terminals. I have wired and tested both configurations hundreds of times in our workshop, and the choice is never as simple as picking one over the other. It depends on your load inertia, your cycle time, and whether your 300N model has the built-in braking unit (the “B” suffix on the nameplate, like 300N-055GB-T4).

How DC Injection Braking Actually Works Inside the Drive
DC injection braking on a VFD is deceptively simple. When the drive receives a stop command and the output frequency drops below the threshold you set in P6-11, the inverter switches off its PWM output and feeds a controlled DC current directly into two of the three motor stator windings. That DC field locks the rotor magnetic field in place. The motor decelerates because the rotating rotor now cuts a stationary flux, inducing currents in the rotor bars that oppose motion. The kinetic energy is dissipated as heat inside the motor itself.
There is no external hardware needed. No braking resistor, no brake chopper IGBT. The drive handles everything through parameters in the P6 group. On our assembly line, I see this used constantly on fan and pump applications where the load has low inertia and a clean stop is enough.
How Dynamic (Resistor) Braking Works
Dynamic braking takes a different path. During deceleration, the motor acts as a generator. The regenerated energy flows back through the inverter’s freewheeling diodes into the DC bus, raising the bus voltage. When the bus voltage crosses the brake chopper’s threshold, the chopper IGBT switches on and dumps current through a braking resistor connected between the P+ and PB terminals. The energy becomes heat in the resistor, not in the motor.
This is the only way to handle high-inertia loads like centrifuges, large flywheels, or vertical hoists where you need rapid, repeatable deceleration. The SHZK 300N models with the “B” designation include a built-in brake unit; for models without it, you add an external braking module.
DC Injection Braking
- Energy dissipated in the motor
- No external resistor required
- Best for low-inertia loads
- Limited braking torque
- Good for final hold at zero speed
- Can cause motor heating with frequent use
Dynamic Resistor Braking
- Energy dissipated in the resistor
- Requires resistor on P+/PB terminals
- Handles high-inertia and vertical loads
- High, repeatable braking torque
- Essential for short cycle times
- Added cost and panel space for resistor
Real Parameters: P6-10 Through P6-14 on the 300N
Here is what you actually set on the keypad. These are the values I use every week during commissioning. All pulled directly from the 300N parameter table.
| Parameter | Function | Range | Default |
|---|---|---|---|
| P6-10 | Downtime (stop) method | 0: Decel to stop / 1: Coast stop | 0 |
| P6-11 | DC braking start frequency | 0.00 Hz to max frequency | 0.00 Hz |
| P6-12 | DC braking wait time | 0.0 s – 100.0 s | 0.0 s |
| P6-13 | DC braking current level | 0% – 100% | 0% |
| P6-14 | DC braking duration | 0.0 s – 100.0 s | — |
| P6-05 | Startup DC brake / pre-excitation current | 0% – 100% | 0% |
Side-by-Side: When I Recommend Each Method
Choose DC Injection Braking When…
- The load is a fan, pump, or light conveyor
- You need the motor to hold at zero speed after stopping
- Stop cycles are infrequent (a few per minute at most)
- Panel space is tight and you cannot fit a braking resistor
- You want zero additional hardware cost
Choose Dynamic Resistor Braking When…
- Load inertia is high (flywheels, large drums, centrifuges)
- The application is a hoist, elevator, or inclined conveyor
- Deceleration time must be short and repeatable
- Stop-start cycles are frequent (10+ per minute)
- You are seeing overvoltage faults (OU) during decel

A Real Case from Our Test Floor
Last month we commissioned a 5.5 kW 300N-005GB-T4 on a textile winding machine. The customer wanted the spindle to stop within 0.8 seconds from 50 Hz. First attempt with DC injection only (P6-11 = 5.00 Hz, P6-13 = 100%, P6-14 = 2.0 s) gave us a stop time of about 3.2 seconds. The motor was getting warm fast, and the deceleration was not consistent because the DC braking torque drops sharply as speed falls.
We switched to dynamic braking, installed a 40 Ω / 2 kW resistor across P+ and PB, and set the deceleration time in P0-11 to 0.8 s. Stop time dropped to 0.75 seconds, completely repeatable, and the motor stayed cool. The resistor got warm but well within its rating. For that application, DC injection was simply the wrong tool.
On the other hand, a 0.75 kW drive on a small exhaust fan needed nothing more than P6-10 = 0, P6-11 = 1.50 Hz, P6-13 = 50%, and P6-14 = 0.8 s. The fan stopped cleanly in under a second. No resistor, no extra cost, no extra wiring. That is where DC injection braking earns its keep.
Combining Both Methods
Nothing stops you from using both. A common pattern I set up on our dynamic braking-capable drives:
- Set P6-10 = 0 (decel to stop) with a normal deceleration ramp
- Let the brake chopper handle regeneration during the ramp through the P+/PB resistor
- Set P6-11 to around 2–5 Hz so DC injection kicks in at the very end
- Use P6-13 and P6-14 to give a short DC pulse that holds the motor at zero
This gives you the high braking torque of the resistor during the main deceleration, plus the zero-speed holding torque of DC injection. It is the best of both worlds for positioning-sensitive applications. For deeper parameter work, check our VFD parameter setup guide.

Wiring Notes for the P+ / PB Terminals
If your 300N model has the built-in brake unit (the “B” in the model code), the brake chopper is already inside the drive. You only need to connect the braking resistor between P+ and PB. Do not connect anything between P+ and the negative bus (N or P-) — that is for the DC bus supply, not the brake circuit.
For models without the built-in brake unit, you must install an external braking module first, then wire the resistor to the module’s output terminals. Always check the wiring guide for your specific frame size. For Modbus-based monitoring of brake duty cycle, our Modbus RTU guide covers the relevant registers.
Related Technical Guides
→ VFD Overvoltage Fault (OU)
Diagnose and fix OU faults, often caused by missing braking resistors.
→ VFD Wiring Guide
Complete terminal-by-terminal wiring reference for the 300N series.
→ VFD Parameter Setup
Step-by-step commissioning walkthrough for first-time startup.
→ VFD Fault Codes
Full fault code table with causes and solutions for every 300N alarm.
→ VFD Overcurrent Fault (OC)
Troubleshoot OC faults that can appear during aggressive braking.
→ All Technical Guides
Browse the full library of VFD application notes and tutorials.
Need help selecting the right VFD?
Contact our engineering team for free application consultation — from braking resistor sizing to full parameter configuration.
📱 WhatsApp: +86 13757750205