Correct wiring is the foundation of a reliable VFD installation. This guide covers the SHZK 300N main circuit — supply, motor, braking and ground — and the control terminals for start/stop, speed reference, relay outputs and RS485. Follow it in order and you will avoid the faults that bring most new installations back to the panel: swapped input/output terminals, missing grounds, and the wrong Sink/Source setting.
Main circuit terminals

- R / S / T — AC supply input (single-phase models use R & T, S is empty). Connect mains here only.
- U / V / W — output to the motor. Connect the 3 motor leads here.
- P+ / PB — braking resistor terminals (external braking unit on larger drives).
- (⊥) / PE — protective earth; connect to a solid, dedicated ground.
Critical rule: never swap R/S/T with U/V/W. Connecting mains voltage to the output terminals destroys the IGBT modules the moment power is applied. This is not covered by warranty, so double-check before energising. The motor must rotate forward (U–V–W); if it runs backward, swap any two of U/V/W — do not change the input side.
Main-circuit wiring best practice
- Size cables and the input breaker/fuses to the rated input current of the drive, not the motor — a 0.75–2.2 kW single-phase drive draws more input current than the motor FLC suggests.
- Fit an AC input reactor or EMC filter where the supply is shared with other converters or power quality is poor; it also protects against surge.
- Use a contactor on the input for emergency-stop isolation, but do not start/stop the motor by cycling the contactor — use the control terminals; repeated power-on charging stresses the capacitors.
- Keep motor cable separate from control and communication cables; cross them at 90° if they must meet. Use shielded motor cable for EMC compliance.
- Ground the drive with the shortest possible PE connection; on a multi-drive panel do not daisy-chain the grounds — star them to a common earth bar.
Control terminals
| DI1–DI5 | Digital inputs 1–5 (opto-isolated) |
| COM | Common terminal for digital inputs |
| AI1 | Analog input 1, 0–10V (voltage / current selectable) |
| AI2 | Analog input 2, 0–10V or 0/4–20mA |
| GND | Analog common (0V reference) |
| +10V | Stable +10V supply for analog potentiometer |
| AO1/AO2 | Analog outputs 1/2, 0–10V or 0/4–20mA |
| HDO | High-speed pulse output / open collector |
| CME | Open-collector / relay output common |
| T1A/T1B/T1C | Relay output: T1A–T1B normally closed, T1B–T1C normally open (contact 3A/250VAC) |
| A+ / B- | RS485 Modbus communication terminals |
| P/+24 | 24V supply / external input control terminals |
Two-wire run command (most common)
For a simple run/stop using a maintained switch, use DI1 as forward run and COM. Close the contact to run, open it to stop. Set the run-command source to terminals (P0-02 = 1). For forward/reverse, use DI1 = forward and DI2 = reverse, with a three-position selector so both cannot be closed together.
Sink vs. Source — set it or the DI will not respond
The digital inputs support two wiring logics, selected by the jumper (P/+24) on the control board:
- Sink mode (NPN): the DI switches to COM; internal +24 V sources the input. This is the typical factory setting.
- Source mode (PNP): the DI switches to an external +24 V; the return goes through COM. Use this when wiring to a PLC with PNP outputs.
If a start command appears dead — the keypad shows the terminal input LED not changing — the jumper/logic is almost always mismatched to the PLC output type. Confirm both sides use the same logic and share a common 0 V.
Speed reference wiring
- Potentiometer (manual speed knob): wiper to AI1, one end to +10V, the other to GND. Set AI1 for 0–10V and the frequency source to AI1 (P0-03 = 2).
- 4–20 mA signal (PLC / sensor): signal positive to AI2, return to GND; select current mode on AI2 and set the 4 mA = 0 % / 20 mA = 100 % range.
- Always use shielded twisted-pair for analog signals with the shield grounded at one end only, and run them well clear of the motor cable — analog noise shows up as speed hunting and can even cause false trips.
RS485 Modbus and relay outputs
For Modbus RTU connect the host A to A+ and B to B-, using shielded twisted pair in a bus (daisy-chain, not star) with 120 Ω termination at both ends; set the drive address, baud and data format in the Pd group. The relay terminals T1A/T1B/T1C give a volt-free contact (up to 3 A at 250 VAC) — configure what it signals, such as “running” or “fault”, via parameter. Use it to drive a panel lamp or send a fault signal to the SCADA system.
From our test bench
Before we energise any panel build, we do a simple two-step check: measure continuity from each PE to the earth bar, and confirm with a meter that mains voltage is present on R/S/T and absent on U/V/W. Those thirty seconds catch the two wiring errors that cause the most — and most expensive — failures: a bad ground and swapped power/output terminals.